Short answer: under NFPA 101 (Life Safety Code) §7.9.3, battery-powered emergency lights and exit signs get a functional test for at least 30 seconds every 30 days and a full 1½-hour (90-minute) test once a year, and the owner keeps written records for the fire code official. Self-testing and computer-based units can replace the manual monthly button test. The details below are what inspectors actually look for. Your jurisdiction may enforce the IFC rather than NFPA 101; the IFC points to the same monthly and annual testing, but confirm the edition your AHJ uses.

For Gilbert commercial buildings: this guide applies to properties across Gilbert · Phoenix Southeast Valley · Maricopa County. Rapid commercial growth creates demand for addressable fire alarm installation. Enforcement is handled by Gilbert Fire Department.

Last updated: 2026-11-16 · Published by Fire Solutions NW · AZ ROC CR-11 Fire Protection Systems · Licensed in 8 states

1

Monthly 30-second functional test

NFPA 101 §7.9.3.1.1

Every required emergency lighting unit and battery-backed exit sign is switched to battery power for at least 30 seconds at 30-day intervals (older editions say monthly, with 3 to 5 weeks between tests). For most fixtures this is the push-to-test button. Each lamp must light at full output for the whole test; a unit that dims or fails gets serviced or replaced.

2

Annual 1½-hour (90-minute) test

NFPA 101 §7.9.3.1.1

Once a year, battery-powered emergency lighting must run for not less than 1½ hours. Normal power has to actually be interrupted for the test, and the equipment must stay fully operational for the full duration. Batteries that cannot hold 90 minutes are the most common annual failure.

3

Written records are required

NFPA 101 §7.9.3.1.1

The owner must keep written records of the monthly and annual tests and visual inspections, available to the authority having jurisdiction. Undocumented tests are treated as tests not performed. A simple log listing each fixture by number and location, the date, the result and who tested it is enough.

4

Self-testing and computer-based units are an alternative

NFPA 101 §7.9.3.1.2–7.9.3.1.3

Self-testing/self-diagnostic units that automatically run a 30-second test every 30 days and show failures on a status indicator can replace the manual monthly test. A visual check of the indicators is still required every 30 days, and the annual 1½-hour test still applies. Computer-based systems that log results automatically are a third option.

5

Exit signs follow the same schedule

NFPA 101 §7.10.9

Exit signs with a battery-operated emergency illumination source are tested the same way: 30 seconds every 30 days and 1½ hours annually. Externally illuminated signs depend on the emergency lighting that serves them.

6

Required illumination levels

NFPA 101 §7.9.2.1

Emergency lighting must provide an initial average of at least 1 foot-candle (and at least 0.1 foot-candle at any point) along the path of egress at floor level for 1½ hours. Levels may decline to an average of 0.6 foot-candle (0.06 minimum) by the end of the 90 minutes, and the maximum-to-minimum ratio cannot exceed 40 to 1. A fixture can pass the button test and still leave a dark stretch of corridor.

7

Generator-supplied emergency lighting

NFPA 101 §7.9.2.4 / NFPA 110

Where emergency lighting is powered by a generator rather than unit batteries, the generator and transfer switch are maintained and tested under NFPA 110, and the 1½-hour battery test does not apply in the same way. Check that the generator test records cover the emergency lighting load.

8

What to do with a failed unit

Replace failed batteries or lamps, or the whole unit, and retest. Note the failure and the repair date in the log. If many units fail the annual test at once, the batteries are usually at end of life together; plan a replacement cycle rather than fixing them one at a time.

Bottom line for Gilbert facility managers

Emergency lighting is one of the few fire-protection items an owner or facility team can test in-house: a monthly 30-second button test, an annual 90-minute discharge, and a log. What inspectors cite most is not failed lights but missing records. If you would rather have a qualified contractor run the annual test and keep the log, schedule it with your other annual inspections.